5.1. Tensile failure at anchor body-grout interface
In this study, the grout axial load distribution under double anchor bodies condition was analyzed to evaluate the effect of relative density on the failure modes of LDCA. The grout strain (\({\epsilon }_{g}\)) measured by the embedded strain gauge and the elastic modulus (\({E}_{g}\)) of the grout evaluated by the unconfined compression test were utilized to evaluate the grout axial load (\(P\)) at the point where the strain gauge was installed as Eq. (5).
$$P={E}_{g}{A}_{g}{\epsilon }_{g}$$
5
Where, \({A}_{g}\): the cross-sectional area of the grout. In this study, a loading system that can apply the same load to each anchor body was applied, so the load applied to the 1st and 2nd anchor bodies is half of the total applied load measured from the load cell. Therefore, the axial load of the 1st anchor body was applied as half of the total applied load, and the axial load of the 2nd anchor body was applied so that the load increment generated on the 2nd anchor body has the same value as half of the total applied load. Figure 9 shows the grout axial load distribution of the double anchor bodies at the initial loading stage. During the initial loading phase, the grout axial load distribution of the double anchor bodies showed very similar behavior regardless of the relative density and anchor body spacing. In the first three load increments (below about 10.5 kN), tensile loads were applied to the grout in the 1st anchor body and compressive loads were applied to the grout in the 2nd anchor body. However, at a load of approximately 13.7 kN, redistribution of grout axial loads occurred in all experimental conditions. The tensile load of the 1st anchor body decreased slightly, and the compressive load of the 2nd anchor body increased significantly. Therefore, it seems that a tensile crack occurred between the 2nd anchor body and the underlying grout at the initial loading stage. In the experiment, a fracture sound occurred inside the LDCA at 13.7 kN loading, and after checking the appearance of the LDCA after the pull-out test, it was confirmed that a tensile crack occurred between the 2nd anchor body and the bottom grout as shown in Fig. 10.
A key observation from the grout axial load analysis during the initial loading phase is that the anchor body-grout tensile failure occurred consistently at the same load, independent of relative density and anchor body spacing. This indicates that the tensile failure of the anchor body-grout interface is determined by the grout's properties used in LDCA construction, rather than the surrounding ground conditions or the configuration of multiple anchor bodies. The grout axial loads recorded under the 2nd anchor body at loadings of 10.5 kN (in tests T3, T4, T7, and T8) were − 2.24, -1.86, -2.69, and − 2.41 kN, respectively, reflecting tensile stresses of 0.9–1.3 MPa in the grout. Given that direct tensile tests on grout reported tensile strengths between 0.45 and 3.2 MPa, it is inferred that the grout under the 2nd anchor body was subjected to tensile loads nearing its tensile strength at 13.7 kN under double anchor bodies conditions. In particular, the tensile crack was observed at the anchor body-grout interface, which is expected to have a bond strength smaller than the tensile strength of the grout itself.
Tensile cracking at the anchor body-grout interface, as observed in the physical model test, is also anticipated to occur in field applications. With a scaling factor of 2 applied to the model LDCA, considering the scaling law, anchor body-grout interface failure is expected in the prototype LDCA under a total applied load of 54.8 kN. This suggests that the second anchor body might undergo tensile failure when 27.4 kN is applied to it. This load represents approximately 8.8% of the maximum load capacity (312 kN) for a single prototype anchor body, using a 12.7 mm diameter 7-wire steel strand. Given that the alignment load is set at 5% of the maximum load in the FHWA performance test [26], anchor body-grout failure could likely occur in field-applied LDCA during the initial load increments, or even while applying the alignment load.
5.2. Overlapping of grout axial load
Figure 11 depicts the distribution of grout axial load with increasing load after anchor body-grout tensile failure. When calculating the axial load of the 2nd anchor body, the tensile load of the grout beneath this anchor body was excluded due to tensile failure, and instead, the compressive load in the lower grout was considered for the calculation of the 2nd anchor body's axial load. The axial load distribution in the grout after the tensile failure exhibited similar patterns across different relative densities but varied with the anchor body spacing. In the 450 mm anchor body spacing condition (Figs. 11(a) and (c)), the axial load in the grout under the 2nd anchor body remained constant despite the increasing load. At a 90% relative density, a sudden increase in tensile load in the grout under the 2nd anchor body occurred at a load of 40.2 kN. However, load-displacement curve analysis indicated that the pull-out behavior started first with the 2nd anchor body, transferring unexpected tensile load to the end of the 1st anchor body. Below a load of 36.8 kN, the axial load in the grout under the 2nd anchor body remained constant, while the compressive stress in the remaining part of the grout increased. In the case of LDCA applied in the field, unlike the physical model test, the length of the 2nd anchor body is designed to be very long, so it is expected that the additional tensile load generated at 90% relative density will not be expressed, and the axial load of the grout under the 2nd anchor body will remain constant after the anchor body-grout tensile failure, as shown in the result at 70% relative density. The direct tensile tests on the grout conducted by Li and Li [15] demonstrated that the grout behaves very brittlely under tensile stress. Therefore, it can be concluded that at the moment of anchor body-grout tensile failure, the 2nd anchor body and the lower grout would have completely separated, leading to the independent behavior of the 1st and 2nd anchor bodies thereafter.
Under the 234 mm anchor spacing condition, residual grout axial load was induced in the grout under the 2nd anchor body at both 70 and 90% relative density (Fig. 11(b) and (d)). The axial load in the grout under the 2nd anchor body increased continuously with the increase of applied load, reaching a compressive load of 1.6 kN at 70% relative density and 1.3 kN at 90% relative density at the ultimate loading step. Therefore, it appears that under the 90% relative density condition, the grout-ground interface failure extended from the 1st anchor body to the grout beneath the 2nd anchor body, similarly to the 70% relative density condition, and grout axial load superposition occurred as shown in Fig. 2(b). In the case of the anchor body spacing condition of 234 mm, the length from the 1st anchor body to the grout under the 2nd anchor body is 384 mm, which is a rather short length, and it is estimated that the difference in the grout-ground interface failure load according to the relative density was not significant.
The pull-out test results for narrow anchor body spacing demonstrate that the grout axial load on the 2nd anchor body can exceed the applied load due to residual axial load in the grout. This suggests that relying solely on the comparison of Eq. (2) with the applied load for evaluating grout compressive stability, as in the current LDCA design method, may lead to unexpected grout failure. To avoid such failures, the spacing between anchor bodies (or the length of each anchor body) should be designed to prevent overlapping axial loads in the grout. Both physical model tests in this study and numerical simulations by Shin et al. [29] have shown the necessity of designing anchor body lengths to avert localized grout-ground interface failures. Table 4 shows the ultimate transfer loads (grout-ground interface failure loads per unit length) provided by the FHWA for designing soil anchor lengths [26], along with the calculated minimum anchor body spacings for various soil conditions. These spacings were determined based on an applied load of 187.2 kN, which is 60% of the prototype strand’s tensile failure load as per the FHWA’s design method, to ensure the full dissipation of the applied load. Current design practices typically involve a 2 m anchor spacing; our findings suggest that a spacing of 2 m or less is adequate to prevent local failures in most soil conditions. However, in very soft soils such as loose silty sand and silty clay, larger anchor body spacings are required to avert local failures, and the conventional 2 m spacing may result in grout failure. Consequently, further research on silt and clay conditions, which exhibit shearing behavior distinct from weathered soil, is essential for a more accurate LDCA design.
Table 4
Minimum anchor body spacing in various soil conditions.
| Soil type | Relative density (SPT N value) | Ultimate transfer load (kN/m) | Min. spacing between anchor body (m) |
| Sand and gravel | Loose (4–10) | 145 | 1.3 |
| Medium dense (11–30) | 220 | 0.9 |
| Dense (31–50) | 290 | 0.6 |
| Sand | Loose (4–10) | 100 | 1.9 |
| Medium dense (11–30) | 145 | 1.3 |
| Dense (31–50) | 190 | 1.0 |
| Sand and silt | Loose (4–10) | 70 | 2.7 |
| Medium dense (11–30) | 100 | 1.9 |
| Dense (31–50) | 130 | 1.4 |
| Silt-clay mixture | Stiff (10–20) | 30 | 6.2 |
| Hard (21–40) | 60 | 3.1 |
5.3. Interference effect of multiple anchor bodies
In this study, grout-ground shear stress was evaluated in each experimental condition to explain the cause of reduction in bearing capacity with relative density and anchor body spacing. Figure 12 shows the grout axial load (\({P}_{x}\)) and grout-ground shear stress (\({\tau }_{x}\)) acting on a compression-type anchor.
As shown in the force equilibrium of the grout element, in a compression-type anchor, the grout axial load decreases as it progresses to the opposite side of the anchor body due to the shear stress generated at the grout-ground interface. Therefore, the grout-ground shear stress of a compression-type anchor with LDCA can be evaluated as shown in Eq. (5) [4, 20, 34]. Since this study evaluated the grout axial load at the points where the embedded strain gauges were installed, the gradient of the grout axial load was used to estimate the average grout-ground shear stress between the points where each gauge was installed.
$${{\tau }}_{x}=-\frac{1}{D\pi }\frac{d{P}_{x}}{dx}$$
5
Figure 13 shows the grout-ground shear stress distribution at the ultimate loading step for the single anchor body condition. The dashed line shows the average grout-ground shear stress over the entire length of the anchor. In the single anchor body condition, the grout-ground shear stress was high at the anchor body regardless of relative density and decreased as it approached the anchor head. Unlike tension-type anchors, in compression-type anchors, compressive stress in the grout is generated, and the normal stress at the grout-ground interface increases due to the Poisson effect [34]. Therefore, the grout-ground shear stress (i.e., grout-ground interface shear strength) is large in the part of the anchor body where the compressive force is large, and the grout-ground shear stress is likely to decrease as the compressive force becomes smaller as it is further away from the anchor body. The average grout-ground shear stress at 70 and 90% relative density is 178.6 kPa and 232.8 kPa, respectively, confirming the high grout-ground shear strength at 90% relative density as expected from the direct shear test.
In this study, the grout-ground shear stress distribution for double anchor bodies was compared with that for a single anchor body to assess the effects of relative density and anchor body spacing on the ultimate bearing capacity. For the shear stress distribution of 2nd anchor body, the position of the 2nd anchor body was set at the bottom (x = 0) for comparison purposes. Figure 14 and Table 5 present the grout-ground shear stress variations depending on relative density and anchor body spacing. the reduction ratio for double anchor bodies was calculated by dividing the average shear stress of the 1st or 2nd anchor body by the average shear stress of the single anchor body. The grout-ground shear stress of the double anchor bodies condition revealed that the 2nd anchor body exhibited lower shear stress than the 1st anchor body across all relative densities and anchor body spacings. In all experimental conditions, the grout-ground shear stress of the 1st anchor body had similar values to the single anchor body, and the 2nd anchor body had a lower grout-ground shear stress than the single anchor body. Consequently, the shear stress reduction in the 2nd anchor body was more pronounced at narrower anchor body spacings, with the 90% relative density condition exhibiting a greater reduction than the 70% relative density condition.
Table 5
Average grout-ground shear strength of double anchor bodies conditions
| No. | Dr (%) | No. of anchor bodies | Spacing (mm) | Average grout-ground shear stress (kPa) | Reduction ratio of grout-ground shear stress |
| T1 | 70 | Single | – | 178.6 | – |
| T3 | Double | 450 | 193.4 (1st anchor body) 143.2 (2nd anchor body) | 1.08 0.80 |
| T4 | Double | 234 | 221.8 (1st anchor body) 125.4 (2nd anchor body) | 1.24 0.70 |
| T5 | 90 | Single | – | 232.8 | |
| T7 | Double | 450 | 225.7 (1st anchor body) 160.2 (2nd anchor body) | 0.97 0.69 |
| T8 | Double | 234 | 239.1 (1st anchor body) 114.3 (2nd anchor body) | 1.03 0.49 |
Since grout-ground interface failure occurred in all experimental conditions, the average grout-ground shear stress at the ultimate loading step can be considered as the grout-ground shear strength generated by each anchor body. Therefore, similar to the group effects on later resistance of the pile foundation, in the double anchor bodies condition, the grout-ground shear strength was reduced by the superposition of the shear fields generated by each anchor body (Fig. 15). In the case of group piles, it is known that the bearing capacity of the pile located in the trailing row is reduced by the interference (shadowing) with the shear field generated by the front row pile [3, 22, 24]. Similarly, in the double anchor body condition, each anchor body behaves independently, so it seems that the shear field generated by the 1st anchor body moved the ground around the 2nd anchor body and reduced the grout-ground shear strength. Furthermore, similar to the group pile effect, where a greater reduction in bearing capacity occurs as the spacing between piles decreases [3, 17, 25, 37], the overlap of the shear field increases as the spacing between anchor bodies decreases, and it is believed that a smaller grout-ground shear strength was generated at the 2nd anchor body. The stress field generated by each anchor body is expected to increase with increasing relative density. Davidson et al. [6] found that the magnitude of the shear field generated during cone penetration tests increased with increasing relative density. Therefore, similar to group piles where group efficiency decreases with increasing relative density [18, 19], double anchor bodies appear to experience greater shear field overlap and lower grout-ground shear strength with increasing relative density. The results of the above studies suggest that applying the same grout-ground interface shear strength along the anchor length, as in the current LDCA design criteria, may overestimate the grout-ground failure load of LDCAs. Therefore, it is necessary to propose a reduction factor based on the spacing of the anchor bodies, similar to that used for group piles, to evaluate the accurate ultimate bearing capacity of LDCAs.